Apc Smart Ups 3000 Manual

Size:Download

English

Smart-UPS®RT

3000/5000/6000 VA 200-240Vac

On this page you find the APC Smart-UPS X 3000VA manual. Please read the instructions in this operator manual carefully before using the product. If you have any questions about your that are not answered in the manual, please share your question in the troubleshooting section on the buttom of this page. Smart-UPS ® RT. 3000/5000/6000 VA 200-240 Vac. Tower/Rack Mount 3U. Uninterruptible Power Supply. 2009 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or affiliated companies.

Tower/Rack Mount 3U

Uninterruptible Power Supply

2009 APC by Schneider Electric. APC, the APC logo, Smart-UPSand PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or affiliated companies. All other trademarks are the property of their respective owners.

990-1289E04/2010

Introduction

Smart

The APC by Schneider Electric Smart-UPSRT is ahigh-performance,uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.

INSTALLATION

Read the Safety Guide before installing the UPS.

Unpacking

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Check the package contents:

UPS (with battery modules disconnected)

Front bezel

Literature kit containing:

Apc Smart Ups 3000 Rackmount

Product documentation, Safety Guide, and Warranty Information

Smart-UPSRT User Manuals CD

Software CD

Serial cable

3000 VA XLI models: three output power cords, two input power cords

5000/6000 VA XLI models: six output power cords, Network Management Card documentation

Specifications

TEMPERATURE

This unit is designed for indoor use

OPERATING

32° to 104° F (0° to 40° C)

only. Select a location sturdy enough to

STORAGE

5° to 113° F (-15°to 45° C) charge the UPS

handle the weight.

battery every six months

Do not operate the UPS where there is

MAXIMUM

excessive dust or the temperature and

ELEVATION

humidity are outside the specified limits.

OPERATING

10,000 ft (3,000 m)

Ensure that the air vents on the front

STORAGE

50,000 ft (15,240 m)

and rear of the UPS are not blocked.

HUMIDITY

0 to 95% relative humidity

WEIGHT

UPS

120 lbs (55 kg)

UPS WITH

140 lbs (64 kg)

PACKAGING

.

1

Wiring and Connecting the UPS

5000/6000 VA XLI MODELSONLY: HARDWIRINGINSTRUCTIONS

Wiring must be performed by a qualified electrician.

Install a high magnetic 30/32 A utility circuit breaker.

Adhere to all national and local electrical codes.

Use #10 AWG gauge (5 mm2) wire.

Apc Smart Ups 3000 Manual

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

Apc 1500 Smart Ups Manual

4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (green: ground, brown: hot, blue: neutral). Use an appropriate strain relief (not included).

5.Switch the utility circuit breaker ON.

6.Check line voltages.

7.Replace the access panel.

CONNECTING THEBATTERY MODULES ANDATTACHING THEFRONTBEZEL

3000

.

3

BASICCONNECTORS

Power management software and interface kits can be used with the UPS.

serial com

Use only interface kits supplied or approved by APC.

Any other serial interface cable will be incompatible with the UPS

connector.

Manual bypass enables the user to manually put connected equipment into

bypass mode.

normal bypass

Emergency Power Off terminal allows the user to connect the UPS to the

central EPO system.

EPO terminal

The UPS features a transient voltage surge-suppression(TVSS) screw for

connecting the ground lead on surge suppression devices such as telephone

TVSS screw

and network line protectors.

When connecting grounding cable, disconnect the unit from the utility

power outlet.

Optional external battery packs provide extended runtime during power

outages. These units support up to ten external battery packs.

external battery

See the APC Web site, www.apc.com for the information on the external

pack connector

battery pack, SURT192XLBP.

5000/6000 VA

XLI models

output circuit breakers

3000/5000/6000 VA XLJ/XLT/XLTW models

output circuit breaker

CONNECTINGEQUIPMENT ANDPOWER TO THEUPS

1.Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models).

2.Avoid using extension cords.

3000 VA XLJ/XLT/XLTW/XLI and 5000/6000 VA XLJ/XLT/XLTW models: Using a power cord, plug the UPS into a two-pole,three-wire, grounded receptacle only.

5000/6000 VA XLJ and 6000 VA XLT models: To draw full power from the UPS have a qualified electrician cut off the input plug and hardwire the UPS to the appropriate power panel.

3.Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.

4.To power up the UPS press the button on the front panel.

The UPS battery charges when it is connected to utility power. The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period.

5.For additional computer system security, install PowerChute® Business Edition Smart-UPSmonitoring software.

OPTIONS

Refer to the APC Web site, www.apc.com for available accessories.

Apc Smart Ups 3000va Manual

External Battery Pack SURT192XLBP

Apc Smart Ups 3000 Specs

Rail Kit SURTRK2

Isolation Transformer

Service Bypass Panel

.

5

OPERATION

Load

SMART-UPS RT FRONTDISPLAY

Battery Charge

Indicator

Description

Online

The Online LED illuminates when the UPS is drawing utility power and performing

double conversion to supply power to connected equipment.

On Battery

The UPS is supplying battery power to the connected equipment.

Bypass

The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility

power is sent directly to connected equipment during bypass mode operation.

Bypass mode operation is the result of an internal UPS fault, an overload condition

or a user initiated command either through an accessory or the manual bypass

switch. Battery operation is not available while the UPS is in bypass mode. Refer to

Troubleshooting in this manual.

Fault

The UPS detects an internal fault.

Refer to Troubleshooting in this manual.

Overload

An overload condition exists. See Troubleshooting.

Replace

The battery is disconnected or must be replaced. See Troubleshooting.

Battery

Feature

Function

Power On

Press this button to turn on the UPS. (See below for additional capabilities.)

Power Off

Press this button to turn off the UPS.

Feature

Function

Cold Start

When there is no utility power and the UPS is off, press and hold the

button to

power up the UPS and connected equipment.

The UPS will emit two beeps. During the second beep, release the button.

Self-Test

Automatic: The UPS performs aself-testautomatically when turned on, and every

two weeks thereafter (by default). During the self-test,the UPS briefly operates the

connected equipment on battery.

Manual: Press and hold the

button for a few seconds to initiate the self-test.

Diagnostic Utility Voltage

The UPS has a diagnostic feature that displays the utility voltage. Plug

the UPS into the normal utility power.

The UPS starts a self-testas part of this procedure. Theself-test

does not affect the voltage display.

Press and hold the

button to view the utility voltage bar graph

display. After a few seconds the five-LED,Battery Charge

display

on the right of the front panel shows the utility input voltage.

Refer to the figure at left for the voltage reading (values are not listed

on the UPS).

The display indicates the voltage is between the displayed value on the

list and the next higher value.

On Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button to silence this alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

When 2 minutes of run time remain the UPS emits a continuous beeping. If PowerChute is not being used, files must be manually saved and the computer must be turned off before the UPS fully discharges the battery.

The UPS battery life differs based on usage and environment. Refer to www.apc.com, for on battery runtimes.

.

Apc Smart Ups 1000 Manual

7

USERCONFIGURABLEITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OPTIONALSMARTSLOT ACCESSORY CARDS ORTERMINALMODE.

Apc Smart Ups 3000 User Manual

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Automatic Self-Test

Every 14 days

Every 7 days(168 hours),

Set the interval at which the

(336 hours)

14 days (336 hours)

UPS will execute a self-test.

On Startup Only,

No Self-Test

UPS ID

UPS_IDEN

Up to eight characters to

Uniquely identify the UPS, (i.e.

define the UPS

server name or location) for

network management purposes.

Date of Last Battery

Manufacture Date

Date of

Reset this date when you replace

Replacement

Battery Replacement

the battery modules.

mm/dd/yy

Minimum Capacity

0 percent

0, 15, 25, 35, 50, 60, 75,

Following a low-battery

Before Return from

90 percent

shutdown, the battery modules

Shutdown

will be charged to the specified

percentage before powering

connected equipment.

Alarm Delay After

5 second delay

5 or 30 second delay

Mute ongoing alarms or disable

Line Failure

At Low Battery

all alarms permanently.

Never

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,

Set the interval between the time

720, 960 seconds

when the UPS receives a

shutdown command and the

actual shutdown.

Duration of

2 minutes

2, 5, 7, 10, 12, 15, 18,

The low battery warning beeps

Low Battery Warning.

PowerChute

20 minutes

are continuous when two

software provides

minutes of run time remain.

automatic,

Change the warning interval

unattended

default to a higher setting if the

shutdown when

operating system requires a

approximately 2

longer interval for shutdown.

minutes of battery

operated runtime

remains.

Synchronized Turn-on

0 seconds

0, 20, 60, 120, 240, 480,

The UPS will wait the specified

Delay

720, 960 seconds

time after the return of utility

power before turn-on(to avoid

branch circuit overload).

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

output voltage

+20%

will pass to connected

setting

equipment during internal

bypass operation.

Next >= Page 1 =12